Boiler Feed Selection Process
Our most common boiler feed systems can be selected using the chart below.
The pumps listed are based on 125psi boiler pressure.
1 |
Select a tank size (gallons of capacity) which is about the same,
or somewhat larger, than your boiler horsepower. |
2 |
Select your construction materials. A steel tank with cast iron/bronze
fitted pump(s) for the lowest initial cost; or an all stainless steel
system for long life and best value. Steel tanks have an average life
of 3-6 years. Stainless tanks are warranted for 20 years, and may be
the last tank you ever need to buy. Cast iron/bronze fitted pumps are
warranted for 1 year; stainless pumps for 5 years. |
3 |
Decide whether you need a simplex or duplex system. A simplex system
(one pump) typically needs no control panel because most boiler manufacturers
include motor starters in their control panel. But if you decide to
go this way, keep a spare pump available to avoid down time.A safer
alternative (if downtime is critical) is to install a duplex (2 pump)
system with alternating control panel (optional). The control will
alternate pump use and if a pump fails, allows you to flip a switch,
and the remaining pump will keep your boiler operating while you repair
the defective pump. |
Our complete system includes: tank, stand, make-up valve,
sight gauge, drain valve, pump(s), isolation valve(s), inlet strainer(s),
and piping |
AERO Vertical Feed Systems with AERO Pumps
SIMPLEX SYSTEMS |
Boiler HP |
Tank Size |
Gallons |
System Model Numbers* |
Aero Pump |
Size (inches NPT) |
HP |
Steel Tank CI/BF Pump Model |
All SS Model |
Pump Suction |
Pump Discharge |
4-6 |
19 x 24 |
29 |
BJCSV1924-2 |
BJSSV1924-2 |
5AERCT5 |
1 |
1 |
1/2 |
7-10 |
19 x 24 |
29 |
BJCSV1924-3 |
BJSSV1924-3 |
5AERCT6 |
1 |
1 |
1/2 |
10-15 |
19 x 30 |
37 |
BJCSV1930-4 |
BJSSV1930-4 |
7AERCT6 |
1 |
1 |
3/4 |
15-25 |
19 x 30 |
37 |
BJCSV1930-44 |
BJSSV1930-44 |
7AERCT7 |
1 |
1 |
3/4 |
15-25 |
19 x 36 |
44 |
BJCSV1936-5 |
BJSSV1936-5 |
7AERCT7 |
1 |
1 |
3/4 |
25-35 |
19 x 36 |
44 |
BJCSV1936-6 |
BJSSV1936-6 |
15AERCS5 |
1 1/4 |
1 |
1-1/2 |
35-45 |
19 x 42 |
52 |
BJCSV1942-7 |
BJSSV1942-7 |
20AERCS6 |
1 1/4 |
1 |
2 |
46-80 |
19 x 42 |
52 |
BJCSV1942-8 |
BJSSV1942-8 |
30AERCS7 |
1 1/4 |
1 |
3 |
60-80 |
19 x 48 |
59 |
BJCSV1948-9 |
BJSSV1948-9 |
30AERCS8 |
1 1/4 |
1 |
3 |
DUPLEX SYSTEMS |
10-30 |
23 X 24 |
43 |
BSCSV2324 |
BJSSV2324 |
7AERCT7 |
1 |
1 |
3/4 |
30-50 |
23 X 30 |
54 |
BJCSV2330 |
BJSSV2330 |
20AERCS2 |
1 1/4 |
1 |
2 |
50-60 |
23 x 36 |
65 |
BJCSV2336 |
BJSSV2336 |
30AERCS7 |
1 1/4 |
1 |
3 |
60-75 |
23 x 42 |
76 |
BJCSV2342 |
BJSSV2342 |
30AERCS8 |
1 1/4 |
1 |
3 |
75-90 |
23 x 48 |
86 |
BJCSV2348 |
BJSSV2348 |
30AERCS8 |
1 1/4 |
1 |
3 |
* add suffix -NS to model number if non-siphon (air